1. News Center
  2. Media Center

Diesel generators safety operation procedures

Date:2013-09-29     Views:2129

1, at 20 ℃, open electric heater, to preheat machine.
2, check whether there is any obstruction operation about the organism along with the surrounding of sundry, if any needs to be removed on time.
3, read the crankcase oil level, and gas tank oil level, radiator groundwater level. For example oil level groundwater level is leaner compared to specified value, must be combined with the regular position.
4, check heating oil supply cooling water valve and globe valve is open position.
5, check the electric start of battery voltage is normal.
6, inspection distribution panel test button, observe the alarm light is ever stand out.
7, read the distribution panel switch in break-brake position, regardless of if the indicator inside instrument from the zero.
8, start the intake and exhaust fan
9, press the engine start button, pass start operating. Should the starting failure, can press the distribution corresponding reset button on the screen, for that alarm to get rid of, the device back to normal state before the second start. Starts, machine normal voice, cooling water pump operation indicator instrument is common, and also the road started successfully. 
(3) the manual operation in parallel power
1, stay and car diesel generators oil temperature, temperature of water, oil pressure to normal functioning.
2, for instance car and the output voltage and frequency from the diesel generators's value is similar to the value about the bus.
3, to be and car diesel generators synchronizer handle inside "closing" position.
4, observe the indicator light of synchronous indicator and pointer.
5, observe synchronization indicator light, completely extinguished or pointer rotation to zero, and electrical switching switch might be.
6, enter and run, then squeeze synchronizer handle cycle "off" position.
7, if synchronizer after closing, synchronizer pointer rotating too quickly or levorotation, isn't allowed and car, otherwise, causes the switch failure.
8, manual and after the success with the car, should immediately connection with lv distribution, the implementation on the total distribution panel can feed the switch switch electric transmission operation.
(4) operation safety management
1, examine the indicating instrument using the regulation time, pay attention to the grease pressure, water temperature changes. Lubricating oil is just not lower than 150 kpa pressure, cooling temperature of water is just not above 95 ℃.
 2, look into the crankcase oil level, oil tank, radiator, waterline, a lesser amount than normal position needs to be added.
3 inside instrument, frequently observed distribution panel and alarm indicator light is common. Those who have fault turns red, said, a green light for the normal operation with the light.
4, check the charger is normal.
5, and pay attention to each part of the machine running sound is typical.
6 our bodies shell, bearing parts, fingerprint casing, tubing, water pipes, have the temperatures are normal.
7, pay attention to focal felt hair machine or electrical equipment such as peculiar smell.
8, found a negative situation, should be resolved an actual-time processing; Serious should stop processing.
9, any downtime, must eliminate the faults, then press the repeat hand button within the unit, the device can operate again.
10, towards running parameters, per shift record not less than two times.
(5) parking 1, the output of total touchscreen feeder switch lock, over grid. 2, diesel generators no-load running 10 minutes after parking. 3, stop blower, cooling water pump room, etc.

QQ客服

QQ客服

在线客服

咨询电话